Q&A for common communication problems of Yudian AI artificial intelligence industrial regulator

Q&A for common communication problems of Yudian AI artificial intelligence industrial regulator
1. What is the data format of the Yudian AI series instrument?
Answer: 1 start bit, 8 data bits, no parity, 1 or 2 stop bits, baud rate range 4800~19200bit/s;





2. What is the parameter number of the PV value during communication? (Maximum question asked by the customer)
Answer: When the UAV AIBUS protocol communicates, whether it is reading or writing (regardless of reading/writing any parameter code), the meter will return the PV value, so there is no specific parameter code for PV (measurement value); It can ensure that when reading and writing any parameter, the PV value can be read at the same time, so that the system does not affect the refresh rate of the PV value due to the read and write operations on the parameter. When using the MODBUS protocol, due to the limitation of the MODBUS protocol itself, the write data is returned when the parameter is written, and the PV value cannot be returned. Therefore, if the write operation is performed, it is necessary to perform a read operation to read the PV value to maintain the real-time PV. The value update frequency.





3. AI series instruments V8.20 or above are compatible with MODBUS-RTU protocol. What are the specific settings and parameter codes?
Answer: The middle H item of the instrument's internal parameter AF parameter is equal to 1, then AF >= 128; the read length is 4 words, there is no specific one for the MODBUS address of PV (measured value) (3.1); Parameter code 00H (SV value) (ADDR = 1), the data sent is 01 03 00 00 00 04 CRCL CRCH (where 01 is the address, 03 is the read function code, 00 00 is the start address, 00 04 is the read Length, last CRC check); reverse data is MODBUS address 40001 = PV (measured value), 40002 = SV (given value), 40003 = MV and alarm status, 40004 = value of the parameter read (example = SV value);
(3.2) If the upper limit alarm is read, the starting address is 00 01 (other parameters such as the lower limit alarm is 00 02), then the data is in 40002~40005, 40002 = PV and so on;
(3.3) Regarding the write function, the current write function of AI instrument only supports single write, and does not support batch write (because batch write will take up a lot of communication time, resulting in PV value cannot be updated in time, affecting the real-time tracking capability of the system), and execution When writing, due to the MODUBS protocol, the meter will not return the measured value PV, only return the written data;





4. What is the register name when the AI ​​series instrument communicates with the Kingview or MCGS software?
Answer: Kingview selects Yuguang - AI series instrument - serial port driver. When editing data dictionary, register name has class, class V and class R, class V register read only: V1 is the measured value, V2 is Given value, V3 is the output value MV, V4 is the alarm state; the R class register is defined by the parameter code in the table of the AIBUS communication protocol, and the letter R is added before each hexadecimal code.
The MCGS selects the driver of the Yuguang smart meter; the meaning of the register is the same as the configuration king.





5, on the AI ​​multi-channel inspection instrument and AI-7048 communication problems?
A: AI multi-channel inspection instrument and AI-7048 communication are compatible with single-channel instrument in standard mode. For example, AI-706M can be equivalent to 6 AI-501, occupying 6 addresses. The ADDR parameter in the instrument is only set. The starting address of the meter, if set to 1, the addresses 1, 2, 3, 4, 5, and 6 are occupied by this table. Any table on the bus must not use these addresses, then the next instrument ADDR > 6; AI-702M occupies two paths, AI-704M occupies 4 channels, AI-7048 also occupies 4 channels; in order to speed up communication, the patrol instrument also has a mode of transmitting 3 channel measurement values ​​at a time, see CF parameter selection in the manual. Function, but the communication protocol is not compatible with single-loop instrument in this mode. The PC software needs special processing and few applications, suitable for occasions where large amounts of data need to be collected quickly.





6. What is the meaning of the AI ​​instrument alarm status?
Answer: The data returned by the instrument during communication contains the alarm status, which is the 6th byte in the returned data. The meaning is as follows:












Regulator and single display (V7.0)



AI-702M/704M/706M



Regulator, thermostat and single display (V7.5)



Bit 0



Upper limit alarm (HIAL)



Upper limit alarm (HIAL)



HIAL



Bit 1



Lower limit alarm (LoAL)



Lower limit alarm (LoAL)



LoAL



Bit 2



Positive deviation alarm (dHAL)



0



HdAL



Bit 3



Negative deviation alarm (dLAL)



0



LdAL



Bit 4



Enter overrange alarm (orAL)



Overrange alarm (orAL)



Oral



Bit 5



AL1 state, 0 is action



0



Alternate (0)



Bit 6



AL2 state, 0 is action



0



0 means MV is the output value, 1 is the status word B.








7. Why is there more than one model when the configuration software calls the Yudian OPC server?



A: When you need to add other instrument models, you can install the YDOPC folder under the roller (usually under C:\Programfiles\YDOPC) to add the configuration file. Which parameters are needed can refer to the parameter code in the AIBUS communication protocol. The table increases or decreases on its own; unneeded parameters should not be read as much as possible.





8. PLC has integrated MODBUS communication command library. Does U-power's watch support MODBUS communication protocol?



A: At present, the table of U2000's V8.20 version supports MODBUS protocol, but some of them do not support MODBUS protocol. Only the communication port of PLC can be used for free protocol communication.
Http://news.chinawj.com.cn Editor: (Hardware Business Network Information Center) http://news.chinawj.com.cn

Aluminum Shell Emergency Driver

LED emergency power supply is a driver that can be used as backup power supply for LED lights . The aluminum shell emergency driver can be applied to all different types of LED lights in the wide range of AC85-265V . Aluminium housing can make the emergency conversion kit faster heat dissipation , small density and light weight , with a strong corrosion resistance . Choose high quality rechargeable lithium ion battery to extend the service life .

Led Emergency Driver Of Aluminum Shell



Emergency Light Kit,Led Emergency Inverter,Led Emergency Backup Driver,Led Light With Emergency Backup

Jiangmen City Pengjiang District Qihui Lighting Electrical Appliances Co., Ltd , https://www.qihuilights.com

This entry was posted in on